DONGGUAN DAXIAN INSTRUMENT EQUIPMENT CO.,LTD

Dongguan Daxian Instrument Equipment Co.,Ltd. CHINA'S LEADER IN TESTING EQUIPMENT Professional Manufacturer of Building Materials 13 years Fire Retardant / Wire/ Plastics/ Rubber/ Environmental

Manufacturer from China
Verified Supplier
8 Years
Home / Products / Fire Testing Equipment /

EN137 Fire Testing Equipment , Mask Flame Resistance Flammability Test Chamber

Contact Now
DONGGUAN DAXIAN INSTRUMENT EQUIPMENT CO.,LTD
Visit Website
City:dongguan
Province/State:guangdong
Country/Region:china
Contact Person:MissSophia Su
Contact Now

EN137 Fire Testing Equipment , Mask Flame Resistance Flammability Test Chamber

Ask Latest Price
Video Channel
Brand Name :DAXIAN
Model Number :DX8220
Certification :CE
Place of Origin :China
MOQ :one set
Price :Negotiation
Payment Terms :L/C,D/A,D/P,T/T,Western Union,MoneyGram,In cash
Supply Ability :15 sets per month
Delivery Time :15work days
Packaging Details :Wooden case
Ambient temperature :-5 °C -30 °C
Relative humidity :≤85%
Power :220V ± 10%, 50HZ, 100W
Air source :propane
Standards :GB/T16556, EN137:2002
Features :Automatic timing, digital display
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

EN137 Fire Testing Equipment , Mask Flame Resistance Flammability Test Chamber

EN137 Mask Flame Resistance Fire Testing Machine

Features: Automatic timing, digital display

Comply to standard: GB/T16556, EN137:2002

Parameters:

1. Ambient temperature: -5 °C -30 °C

2. Relative humidity: ≤85%

3. Supply voltage and power: 220V ± 10%, 50HZ, 100W;

4. The burner flame 250mm temperature of 950 °C ± 50 °C

5. Adjustable flame time steplessly adjustable

6. Air source: propane

7. Test sample: mask.

Test steps:

1 Turn on the instrument's power supply and air supply. Check whether the “pressure adjustment”, “flow adjustment”, and “long light adjustment” on the instrument panel are in the closed position.

2. Open the test box door, move the head mold and install the test sample on the head mold. After adjusting the distance from each burner to the test sample to 250 mm according to the national standard, manually remove the sample from the burner.

3. Turn on the power switch and gas source valve on the instrument, adjust the “long light adjustment” knob on the panel, and turn on the long light with an open flame. The flame length is about 20mm. Press the display “?” key on the instrument panel and then press the “▲” key. The display shows “1005”.

Adjust the "pressure adjustment" on the instrument so that the indicated value of the pressure gauge is around 0.12 Mpa.

4. Press the "Run" button to adjust the "flow adjustment". At this point, the burner is on, adjust the air feed nut at the lower end of the burner. Measure the temperature of the 250mm flame at the temperature of (950 ± 50) °C with the thermometric meter, press " "Reset" button burner flame goes out.

5. After adjusting the display on the panel, press the "?" key, and then press the "▲" key to display "0005". Manually move the test sample to the test position. Press the "Run" key to point the burner. The display will start timing. After 5 seconds, the burner will be extinguished automatically, and the afterburning time will begin to time. Observe whether there is a continuous burning after the flame is applied to the sample. If the burning continues, press the “Timer” button on the instrument to stop the display.

6. Record the continued burning time and the observed phenomenon.

7. Replace the new sample and repeat 3.2-3.6 operation. After the test is completed, turn off the power supply and air supply, and clean and maintain the combustion box.

Packing list:

1 Test chamber and head mold 1 station

2 medium pressure valve 1 only

3 Power cord 1

4 Fuse 0.5A 2 only

5 Rubber hose 1.5 meters

6 Instructions 1

7 Certificates 1

EN137 Fire Testing Equipment , Mask Flame Resistance Flammability Test Chamber

Inquiry Cart 0