DONGGUAN DAXIAN INSTRUMENT EQUIPMENT CO.,LTD

Dongguan Daxian Instrument Equipment Co.,Ltd. CHINA'S LEADER IN TESTING EQUIPMENT Professional Manufacturer of Building Materials 13 years Fire Retardant / Wire/ Plastics/ Rubber/ Environmental

Manufacturer from China
Verified Supplier
8 Years
Home / Products / Wire Testing Equipment /

Single Combustion Testing Equipment For Building Materials Or Products Determine The Fire Reactivity Of Building Materi

Contact Now
DONGGUAN DAXIAN INSTRUMENT EQUIPMENT CO.,LTD
Visit Website
City:dongguan
Province/State:guangdong
Country/Region:china
Contact Person:MissSophia Su
Contact Now

Single Combustion Testing Equipment For Building Materials Or Products Determine The Fire Reactivity Of Building Materi

Ask Latest Price
Video Channel
Brand Name :DAXIAN
Model Number :DX8362
Certification :EN13823
Place of Origin :China
MOQ :One set
Price :Negotiation
Payment Terms :L/C,D/A,D/P,T/T,Western Union,MoneyGram,In cash
Supply Ability :15 sets per month
Delivery Time :15 work days
Packaging Details :Wooden case
Standard :EN13823, GB/T 20284-2006
Application :of building materials or articles (excluding flooring materials and products specified in EC Decision 2000/147/EC)
Function :determine the fire reactivity of building materials or articles
Smoke exhaust speed :0.50 cubic meters/s ~ 0.65 cubic meters/s
Temperature measurement accuracy :0.5°C
Signal output :4-20mA
Relative humidity :<90% (no condensation)
Refoldability :<±1% control cabinet internal structure
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

DX8362 Single Combustion Testing Equipment for Building Materials or Products

Single Combustion Testing Equipment For Building Materials Or Products Determine The Fire Reactivity Of Building Materi

Comply with the standard:

It meets the requirements of GB/T 20284-2006 standard "Monomer Combustion Test of Building Materials or Products" and the EN13823 "Monomer Combustion Test Method (SBI)" test standard requirements.

Scope of application:

A method used to determine the fire reactivity of building materials or articles (excluding flooring materials and products specified in EC Decision 2000/147/EC) in the Single Combustion Test (SBI).

Performance parameters:

The equipment includes a combustion test room, a control room, a trolley, a smoke exhaust pipe, a data collection and analysis device, and a gas supply control device.

1.Combustion test room: L3000*W3000*H2400(MM), the top of the room is connected with the sampling pipe collection hood and smoke exhaust pipe, there is a space under the cart for air to enter and exit naturally. During the test, the heat released by the combustion of the sample and the combustion products should be discharged from the smoke exhaust pipe and built with a brick wall.

2. Ignition source, 31KW propane right-angle sandbox burner (side length 250MM and height 80MM) placed in the vertical corner of the cart.

3. A comprehensive sampling area is provided in the smoke exhaust pipe for placing sensors and sampling pipes.

4. Smoke exhaust speed: 0.50 cubic meters/s ~ 0.65 cubic meters/s.

5. The ambient temperature measurement in the laboratory: K-type armored thermocouple with a diameter of 1MM, environmental pressure test: ±200Pa.

6. Exhaust flue temperature measurement: imported K-type armored thermocouple with a diameter of 0.5.

7. Temperature measurement accuracy: 0.5°C.

8. High-precision pressure sensor for exhaust flue, with an accuracy of ±2Pa

9. Time recording system accuracy: 0.1S.

10. Test time: 1~30 minutes adjustable setting.

11. The smoke density measurement system can measure the smoke density in the test process.

12. The gas analyzer and key components are all imported originally.

13. With embedded computer and 8.4-inch LCD display, with TCP/IP and RS-232 communication interface options

14. Oxygen measurement:

1. Measuring range: 0-25%

2. Signal output: 4-20mA;

3. Response time T90: ≤2S;

4. Ambient temperature: 0-45°C;

5. Relative humidity: <90% (no condensation);

6. Linearity: <±0.1% O2;

7. Zero drift: 0.05% O2 (one week);

8. Repeatability: <±0.02% O2;

15. Carbon dioxide (CO2) measurement:

1. Measuring range: 0-10%

2. Refoldability: <±1% control cabinet internal structure

Zero drift: ≤2%/week

Range drift: ≤2%/week

3. Linearity: <±1%

4. Response time: T90≤2 seconds

16. The data acquisition system can collect and record test data such as oxygen concentration, carbon monoxide concentration, temperature, smoke density, heat release rate, mass loss rate, etc., which can be saved.